Schneider Electric Original Contactor 150A 100HP LC1D150G7

$247.99
Brand
Schneider Electric
Current Type
AC
Maximum Amperage
150 A
Horsepower
100 hp
Number of Phases
3
Coil Voltage
120 V
Current Rating
150 A
Number of Poles
3-Pole
MPN
LC1D150G7
UPC
3389110527537
condition
New

Messages are responded to Monday-Friday 8 AM to 4 PM Central Time.  Please message us for additional photos or details.

 

If you would like expedited shipping, please message us BEFORE placing the order so we can add the shipping service/cost to the listing.  We can ship on your FedEx or UPS account- message us BEFORE placing the order or leave a buyer’s note on the order with your account number.  We do not use USPS.

 

International orders are shipped using the eBay International Shipping Program.  If you would like us to ship internationally with a different service, message us BEFORE placing the order.

 

Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control
Resistive load
Utilisation category
AC-3
AC-1
AC-4
AC-3e
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 1000 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
200 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
150 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
150 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit
[Uc] control circuit voltage
120 V AC 50/60 Hz
Motor power kW
40 kW at 220...230 V AC 50/60 Hz (AC-3)
75 kW at 380...400 V AC 50/60 Hz (AC-3)
80 kW at 415...440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660...690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
40 kW at 220...230 V AC 50/60 Hz (AC-3e)
75 kW at 380...400 V AC 50/60 Hz (AC-3e)
80 kW at 415...440 V AC 50/60 Hz (AC-3e)
90 kW at 500 V AC 50/60 Hz (AC-3e)
100 kW at 660...690 V AC 50/60 Hz (AC-3e)
75 kW at 1000 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating
40 hp at 200/208 V AC 50/60 Hz for 3 phase motors
50 hp at 230/240 V AC 50/60 Hz for 3 phase motors
100 hp at 460/480 V AC 50/60 Hz for 3 phase motors
125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 104 °F (40 °C) - 10 min for power circuit
580 A 104 °F (40 °C) - 1 min for power circuit
1200 A 104 °F (40 °C) - 10 s for power circuit
1400 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
250 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole
24 W AC-1
13.5 W AC-3
13.5 W AC-3e
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1
B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
8 Mcycles
Electrical durability
0.85 Mcycles 150 A AC-3 <= 440 V
1 Mcycles 200 A AC-1 <= 440 V
0.85 Mcycles 150 A AC-3e <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.5 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.15 Uc -40…131 °F (-40…55 °C) operational AC 50/60 Hz
1...1.15 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
Inrush power in VA
280…350 VA 60 Hz cos phi 0.9 (at 68 °F (20 °C))
280…350 VA 50 Hz cos phi 0.9 (at 68 °F (20 °C))
Hold-in power consumption in VA
2…18 VA 60 Hz cos phi 0.9 (at 68 °F (20 °C))
2…18 VA 50 Hz cos phi 0.9 (at 68 °F (20 °C))
Heat dissipation
3…4.5 W at 50/60 Hz
Operating time
20...35 ms closing
40...75 ms opening
Maximum operating rate
1200 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Power circuit: connector 1 0.02…0.19 in² (10…120 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 1 0.02…0.19 in² (10…120 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 1 0.02…0.19 in² (10…120 mm²) - cable stiffness: solid without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end
Tightening torque
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.21 lbf.in (12 N.m) connector hexagonal 0.16 in (4 mm)
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support
Rail
Plate